I've installed an APC BX950MI-GR and connected it to my Proxmox server via USB. It works: it turns off the server after x minutes after the power loss and it gets turned off by the command upsdrvctl shutdown, when the powers come back on, the UPS turns on and so does the server. The problem is if the power comes back after the server receive the power off signal and before the UPS powers off, in this case the UPS simply goes back in the normal state and the server...stays off. How can I turn it back on? Thanks!

you are viewing a single comment's thread
view the rest of the comments
[–] Cyber@feddit.uk 1 points 6 days ago

Yeah, I get that... I'd be the same

So... are you shutting down after x minutes, or, NUT's signalling to shutdown when the battery is getting low, which is x minutes. (If you see my point) - if the battery still has plenty of capacity, maybe extend the runtime and that might be enough to ride through at least some outages?